– 3 –
PROGRAMMING FORM
Entries apply to the FA168CPS/FA168CPSSIA and
FA148CP/FA148CPSIA
controls, except entries shown in dashed boxes, which apply
only to
the FA168CPS
/FA168CPSSIA
(partition entries) and are not applicable to the FA148CP/FA148CPSIA controls
.
SIA-Compliant Controls: Where noted, certain fields have special settings when used with the FA168CPSSIA and FA148CPSIA SIA-Compliant
controls (indicated by
SIA-Compliant Controls
in reverse type and heavy borders for easy identification).
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
SIA Guidelines for Non-SIA-Compliant Controls: Notes in certain fields give instructions for programming the FA168CPS/FA148CP for False
Alarm Reduction (these controls can be programmed to reduce false alarms, but they are not fully SIA compliant).
Field Function Data Entries Programmable Values
SYSTEM SETUP (
✱
20–
✱
29)
✱
20 INSTALLER CODE
| | | [4112]
4 digits, 0–9
✱
21 QUICK ARM ENABLE
[0,0]
Part. 1 Part.2
0 = no; 1 = yes
✱
22 RF JAM OPTION
[0]
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
✱
23 QUICK (FORCED) BYPASS
[0,0]
Part. 1 Part. 2
0 = no quick bypass UL: must be “0”
1 = allow quick bypass (code + [6] + [#] )
✱
24 RF HOUSE ID CODE
| | |
Part. 1 Part. 2 Common
00 = disable all wireless keypad usage [00,00,00]
01–31 = using 5827, 5827BD or 5804BD keypad
✱
26 CHIME BY ZONE
[0]
0 = no; 1 = yes (select zones to chime on zone list 3,
using *81 Menu mode)
✱
27
POWERLINE CARRIER DEVICE (X–10)
HOUSE CODE
[0]
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G,
7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N,
#14 = O, #15 = P UL: not for fire or UL installations
✱
28 ACCESS CODE FOR
PHONE MODULE
| [00]
(Partition 1 only)
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11
for "
✱
", or # + 12 for "#".
UL: must be “00” for UL Commercial Burg. installations
✱
29 LONG RANGE RADIO OUTPUT
[0]
0 = disable; 1 = enable
✱
31 SINGLE ALARM SOUNDING per ZONE
[0]
0 = unlimited sounding; 1 = one alarm sounding per zone
SIA-Compliant Controls: If “0,” “alarm sounding per zone” will be
the same as the “number of reports in armed period” set in field
*93 (1 if 1 report, 2 if 2 reports, unlimited for zones in zone list 7).
✱
32 FIRE ALARM SOUNDER TIMEOUT
[0]
0 = sounder stops at timeout;
1 = no sounder timeout UL: must be “1” for fire install.
✱
33 ALARM SOUNDER (BELL) TIMEOUT
[1]
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min;
UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4)
✱
34 EXIT DELAY
UL: see inst. instr. for requirements.
| | [60,60]
Part. 1 Part. 2
Common zones use same
delay as partition 1.
00 - 96 = 0 - 96 secs; 97 = 120 secs
SIA Guidelines: minimum exit delay is 45 seconds
SIA-Compliant Controls: 45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result in a 45-second delay.
✱
35 ENTRY DELAY #1 (zone type 01)
For UL Residential Burglary Alarm installations, must be
set for a maximum of 30 seconds; entry delay plus dial
delay should not exceed 1 min. For UL Commercial
Burglar Alarm, total entry delay may not exceed 45 secs.
| | [30,30]
Part. 1 Part. 2
Common zones use same
delay as partition 1.
00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180 secs;
99 = 240 secs (
SIA Guidelines: minimum entry delay is 30 secs)
SIA-Compliant Controls: 30-96 = 30 - 96 secs; 97 = 120 secs;
98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result in a 30-second delay.
✱
36 ENTRY DELAY #2 (zone type 02)
| | [30,30]
Part. 1 Part. 2
See *35 Entry Delay 1 above for entries.
∗
∗∗
∗37 AUDIBLE EXIT WARNING
[1,1]
0 = no; 1 = yes SIA Guidelines: must be enabled
SIA-Compliant Controls: Feature always enabled; field removed.
✱
38 CONFIRMATION OF ARMING DING
[0,0]
Part. 1 Part. 2
0 = no; 1 = yes (wired keypads and RF); 2 = yes, RF only
UL: must be “1” for UL Commercial Burglar Alarm inst.
✱
39 POWER UP IN PREVIOUS STATE
[1]
0 = no; 1 = yes UL: must be “1” SIA Guidelines: must be “1”
SIA-Compliant Controls: Feature must be enabled (enter 1).
DIALER PROGRAMMING (
✱
40 –
✱
42) Do not fill unused spaces. Enter 0–9; #+11 for '
✱
'; #+12 for '#'; #+13 for a 2-second pause. If
fewer than the maximum digits entered, exit the field by pressing [∗]. The next data field number is displayed.
✱
40 PABX ACCESS CODE or
CALL WAITING DISABLE
NOTES: 1.
The call waiting disable feature
cannot be used on a PABX line.
2. Using Call Waiting Disable on a non-call
waiting line will prevent successful
communication to the central station.
| | | | | Enter up to 6 digits. To clear entries, press ✱40✱. If call waiting
used, enter call waiting disable digits “∗ (#+11) 70” plus “# + 13” (pause).
SIA-Compliant Controls: If call waiting is used, enter call waiting disable digits as described
above, and also set Call Waiting Disable option in field *91.